Schneider
A9F74116
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F74116 is a 16‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N series, featuring a C‑curve tripping characteristic (magnetic threshold at 8 × In). The C‑curve provides an ideal balance between overload protection and tolerance of moderate inrush currents, making it a versatile solution for general‑purpose distribution – including lighting circuits, socket outlets, small power feeders, and control panels in commercial, industrial, and residential installations. This MCB delivers a rated ultimate breaking capacity of 10 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard, and 6 kA at 230 V AC per the residential EN/IEC 60898‑1 norm, ensuring reliable fault interruption across a broad spectrum of applications. It is certified to both standards, allowing seamless integration into mixed‑use projects. Designed with Class‑2 insulation for enhanced operator safety, the breaker also offers full coordination with Acti 9 RCDs and Compact NSX MCCBs, simplifying system design. The device incorporates the field‑proven VisiTrip fault‑finder window, which instantly highlights the tripped pole to reduce downtime, and the VisiSafe green strip that delivers undeniable visual confirmation of contact separation – a critical safety feature for maintenance personnel. Its quick‑make/quick‑break mechanism, independent of handle position, ensures consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it optimises panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm² with a 2 N·m torque. The device offers IP20 terminal protection and IP40 when enclosed, operates reliably from -35 °C to +70 °C, and is built with halogen‑free plastics, PVC‑free materials, and silicone‑free construction, achieving a 54% recyclability rate and a total lifecycle carbon footprint of 14 kg CO₂ eq. – all reflecting Schneider Electric’s commitment to sustainable energy management.
Parameter | Details |
|---|---|
General | |
Product Model | A9F74116 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 16 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 36 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 27 kA (75% x Icu) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 15 kA (100% x Icu) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | Yes |
POPs | No POPs |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26F71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | No |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 2.0 cm × L 9.5 cm; weight 110 g |
Package 2 (Box of 12) | 12 units; H 8.2 cm × W 9.8 cm × L 22.5 cm; weight 1.375 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 15.595 kg |
Carbon Footprint (Lifecycle) | |
Total | 14 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 13 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |