Schneider
A9F89263
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F89263 is a high‑capacity two‑pole (2P) miniature circuit breaker from Schneider Electric’s Acti9 iC60H series, rated at 63 A with a C‑curve tripping characteristic (magnetic threshold at 8 × In). Designed to protect both poles simultaneously, this 2‑pole device ensures complete disconnection of phase and neutral in single‑phase AC systems or both lines in DC installations, delivering superior isolation and safety for heavy‑duty distribution circuits – including large lighting banks, power feeders, HVAC equipment, motor control panels, and industrial distribution boards. The C‑curve offers a well‑balanced response between overload protection and tolerance of moderate inrush currents, making it a versatile choice for a wide range of demanding applications. This MCB delivers a robust ultimate breaking capacity of 30 kA at 220‑240 V AC (per IEC 60947‑2) and 10 kA at 400 V AC (per IEC 60898‑1), ensuring reliable fault clearing in the most demanding industrial and commercial environments. It is dual‑certified to both industrial and residential standards, offering flexibility across project types. The breaker features the intuitive VisiTrip indicator, which instantly identifies the tripped pole for fast fault diagnosis, and the VisiSafe green strip that provides clear visual proof of contact opening – a critical safety feature for maintenance crews. Its quick‑make/quick‑break mechanism, independent of handle position, ensures consistent performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 36 mm width (4 modular pitches) and DIN‑rail mounting, it saves panel space, while the terminals accept rigid conductors up to 35 mm² and flexible up to 25 mm² with a 3.5 N·m torque. Operating reliably from -35 °C to +70 °C, this MCB is built with PVC‑free materials and achieves 54% recyclability, though it contains halogen above thresholds. Its total lifecycle carbon footprint is quantified at 63 kg CO₂ eq., reflecting Schneider Electric’s transparent environmental reporting.
Parameter | Details |
|---|---|
General | |
Product Model | A9F89263 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60H |
Device Application | Distribution |
Poles Description | 2P |
Number of Protected Poles | 2 |
Rated Current (In) | 63 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) – EN/IEC 60947‑2 | |
– 12…133 V AC 50/60 Hz | 42 kA |
– 220…240 V AC 50/60 Hz | 30 kA (as per product image) |
– 380…415 V AC 50/60 Hz | 15 kA |
– 440 V AC 50/60 Hz | 10 kA |
– ≤125 V DC | 15 kA |
Breaking Capacity (Icu) – EN/IEC 60898‑1 | |
– 400 V AC 50/60 Hz | 10,000 A (as per product image) |
Service Breaking Capacity (Ics) – EN/IEC 60947‑2 | |
– 12…133 V AC | 21 kA (50%) |
– 220…240 V AC | 15 kA (50%) |
– 380…415 V AC | 7.5 kA (50%) |
– 440 V AC | 5 kA (50%) |
– ≤125 V DC | 15 kA (100%) |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…133 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Padlocking Provision | Not specified, but typical for series – padlockable |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between phases |
Number of Pitches | 4 (36 mm total width) |
Width | 36 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.25 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…35 mm² |
Flexible Conductor (copper) | 1…25 mm² |
Flexible with Ferrule (copper) | 1…25 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Multiple Conductors (with accessory) | Up to 3 x 16 mm² rigid or 3 x 10 mm² flexible |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 3.5 N·m (top or bottom) |
Earth‑leakage Protection | Separate add‑on block (Vigi iC60) required |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free status | Product contains halogen above thresholds (not halogen‑free) |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.3 cm × W 3.6 cm × L 9.4 cm; weight 263 g |
Package 2 (Box of 6) | 6 units; H 8.2 cm × W 9.9 cm × L 22.4 cm; weight 1.637 kg |
Package 3 (Pallet of 66) | 66 units; H 30 cm × W 30 cm × L 40 cm; weight 18.464 kg |
Carbon Footprint (Lifecycle) | |
Total | 63 kg CO₂ eq. |
Manufacturing (A1‑A3) | 2 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 60 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.8 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |