Schneider
A9F55206
$100
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F55206 is a two‑pole (2P) miniature circuit breaker from Schneider Electric’s Acti9 iC60H family, rated at 6 A with a D‑curve tripping characteristic. The D‑curve, with its high magnetic threshold (12 × In), is specifically designed for circuits that experience significant inrush currents – think motor starters, transformers, solenoid valves, and capacitive loads – where B‑ or C‑curve breakers would trip unnecessarily. This 2‑pole device protects both poles simultaneously, making it ideal for single‑phase AC or DC applications requiring complete line isolation. It delivers a robust ultimate breaking capacity of 30 kA at 220‑240 V AC (per IEC 60947‑2) and 10 kA at 415 V AC (per IEC 60898‑1), ensuring reliable fault clearance across industrial and commercial installations. The breaker is dual‑certified to both industrial and residential standards, offering flexibility in mixed‑use environments. It features the intuitive VisiTrip indicator window, which instantly reveals the tripped pole to slash troubleshooting time, and the VisiSafe green strip that provides undeniable visual proof of contact separation – a critical safety feature for maintenance crews. Its quick‑make/quick‑break mechanism, independent of handle position, guarantees consistent performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 36 mm width (4 modular pitches) and DIN‑rail mounting, it optimises panel space, while the double‑tunnel terminals accept conductors up to 25 mm² (rigid) and 16 mm² (flexible). Operating reliably from -35 °C to +70 °C, this MCB is built with halogen‑free plastics and PVC‑free materials, achieving 54% recyclability and a total lifecycle carbon footprint of 16 kg CO₂ eq. – all reflecting Schneider Electric’s commitment to sustainable and safe energy distribution.
Parameter | Details |
|---|---|
General | |
Product Model | A9F55206 |
Range | Acti9 |
Product Name | Acti9 iC60H |
Device Short Name | iC60H |
Poles Description | 2P |
Number of Protected Poles | 2 |
Rated Current (In) | 6 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | D |
Magnetic Tripping Limit | 12 x In ± 20% |
Breaking Capacity (Icu) – EN/IEC 60947‑2 | |
– 12…60 V AC 50/60 Hz | 42 kA (from PDF; higher than 30kA at 220‑240V) |
– 100…133 V AC 50/60 Hz | 30 kA |
– 220…240 V AC 50/60 Hz | 30 kA (as per product image) |
– 380…415 V AC 50/60 Hz | Not specified, but likely derated |
– 12…60 V DC | 20 kA (from PDF) |
– 60…72 V DC | 15 kA (from PDF) |
Breaking Capacity (Icu) – EN/IEC 60898‑1 | |
– 240 V AC 50/60 Hz | 10,000 A (as per image) |
– 415 V AC 50/60 Hz | 10,000 A (as per image) |
Service Breaking Capacity (Ics) – EN/IEC 60947‑2 | |
– 10…60 V AC | 21 kA (50%) |
– 100…133 V AC | 15 kA (50%) |
– 220…240 V AC | 7.5 kA (50%) – from PDF |
– 12…60 V DC | 20 kA (100%) |
– 60…72 V DC | 15 kA (100%) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (DIN rail) |
Mounting Support | 35 mm symmetrical DIN rail |
Number of Pitches | 4 (36 mm total width) |
Width | 36 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.25 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Double tunnel terminals (top and bottom) |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Padlocking Provision | Yes (padlockable) |
Earth‑leakage Protection | Separate add‑on block (Vigi iC60) required |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Bulgaria (BG) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; dimensions not specified in provided data; weight approx. 0.25 kg |
Package 2 (Box) | Not specified |
Package 3 (Pallet) | Not specified |
Carbon Footprint (Lifecycle) | |
Total | 16 kg CO₂ eq. |
Manufacturing (A1‑A3) | 2 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 14 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.6 kg CO₂ eq. |