The Acti9 Vigi iC60 A9V39463 is a four-pole add-on residual current device intended for assembly with Acti9 iC60 or Reflex iC60 circuit breakers. It delivers earth leakage protection with a 1000 mA sensitivity and employs Type A-SI (Super Immunised) technology, which improves resilience to electrical interference and contaminated or corrosive settings. The device operates at 400–415 V AC and meets IEC/EN 61009-1. It safeguards against indirect contact electric shock and fire hazards, and its voltage-independent tripping ensures reliable performance. Measuring 135 mm wide, 91 mm high, and 73.5 mm deep, it weighs 0.245 kg and occupies seven 9 mm pitches on a DIN rail. It offers IP20 terminal protection and IP40 when installed in a modular enclosure. The unit functions between -25 °C and +60 °C and can be stored from -40 °C to +85 °C. With a 500 V AC insulation rating, 6 kV impulse withstand, and pollution degree 3, it is suitable for demanding environments. Its carbon footprint is 8 kg CO2 eq. and recyclability potential is 28%.
Parameter | Details |
|---|---|
General | |
Product Model | A9V39463 |
Range | Acti9 |
Product Name | Acti9 Vigi iC60 |
Product or Component Type | Add-on residual current device |
Poles Description | 4P |
Rated Current | 63 A |
Electrical Characteristics | |
Rated Operational Voltage (Ue) | 400…415 V AC |
Earth Leakage Sensitivity | 1000 mA |
Earth Leakage Protection Class | Type A-SI (Super Immunised) |
Residual Current Tripping Technology | Voltage independent |
Rated Insulation Voltage (Ui) | 500 V AC |
Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Standards | EN 61009-1, IEC 61009-1 |
Mechanical & Physical | |
Mounting Support | DIN rail |
Number of 9 mm Pitches | 7 |
Width | 135 mm |
Height | 91 mm |
Depth | 73.5 mm |
Net Weight | 0.245 kg |
Connections | |
Terminal Type | Tunnel type terminal (downside) |
Rigid Conductor | 1…35 mm² |
Flexible Conductor | 1…25 mm² |
Flexible with Cable End | 1…25 mm² |
Wire Stripping Length | 14 mm (bottom connection) |
Tightening Torque | 3.5 N·m (bottom) |
Environmental | |
Degree of Protection | IP20 conforming to IEC 60529 |
Pollution Degree | 3 conforming to IEC 60947-2 |
Electromagnetic Compatibility | 8/20 μs impulse withstand, 3000 A conforming to IEC 61009-1 |
Operating Temperature | -25…60 °C |
Storage Temperature | -40…85 °C |
Packaging | |
Package 1 (PCE) | 1 unit; H 8.6 cm × W 11.5 cm × L 14.1 cm; weight 253 g |
Package 2 (S03) | 15 units; H 30 cm × W 30 cm × L 40 cm; weight 4.405 kg |
Sustainability | |
Carbon Footprint – Total | 8 kg CO₂ eq. |
Carbon Footprint – Manufacturing (A1-A3) | 2 kg CO₂ eq. |
Carbon Footprint – Distribution (A4) | 0.1 kg CO₂ eq. |
Carbon Footprint – Installation (A5) | 0.1 kg CO₂ eq. |
Carbon Footprint – Use Phase (B2, B3, B4, B6) | 6 kg CO₂ eq. |
Carbon Footprint – End-of-life (C1-C4) | 0.5 kg CO₂ eq. |
Recyclability Potential | 28% |
SCIP Number | B078722f-7853-4e1e-a05b-29638f57b0ab |
EU RoHS Directive | Compliant By Exemption |
REACH Regulation | Reference contains SVHC above threshold |
POP Directive | No POPs |
Halogen-free | Halogen free plastic parts product |
PVC free | Yes |
Packaging with Recycled Cardboard | No |
Packaging without Single-use Plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |