Schneider
A9F74140
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F74140 is a 40‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N series, designed with a C‑curve tripping characteristic (magnetic trip at 8 × In). This C‑curve delivers a well‑balanced response between overload protection and tolerance of moderate inrush currents, making it an ideal choice for general distribution applications – including lighting networks, socket outlets, small motor feeders, and control panels – across commercial, industrial, and residential settings. The device complies with both the EN/IEC 60947‑2 industrial standard and the EN/IEC 60898‑1 residential norm, ensuring seamless integration in mixed‑use projects. With an ultimate breaking capacity of 10 kA at 220‑240 V AC (IEC 60947‑2) and 6 kA at 230 V AC (IEC 60898‑1), it guarantees robust fault clearing even in demanding environments. The breaker features the well‑known VisiTrip window, which visually identifies the tripped pole to slash troubleshooting time, and the VisiSafe green strip that provides undeniable proof of contact separation – a vital safety check for maintenance personnel. Its quick‑make/quick‑break mechanism, independent of handle position, ensures consistent performance over 10,000 electrical and 20,000 mechanical cycles. Despite its 40 A rating, the device retains a compact 18 mm width (2 modular pitches) and clips onto DIN rails, saving valuable panel space. The terminals are engineered for heavy‑duty wiring, accepting rigid conductors up to 35 mm² and flexible up to 25 mm² with a 3.5 N·m torque. The breaker offers IP20 terminal protection and IP40 when enclosed, operates from -35 °C to +70 °C, and is built with halogen‑free plastics, PVC‑free construction, and a 54% recyclability rate. Its total lifecycle carbon footprint is quantified at 21 kg CO₂ eq., all transparently disclosed in line with Schneider Electric’s sustainability commitments.
Parameter | Details |
|---|---|
General | |
Product Model | A9F74140 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 40 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 36 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 27 kA (75% x Icu) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 15 kA (100% x Icu) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…35 mm² |
Flexible Conductor (copper) | 1…25 mm² |
Flexible with Ferrule (copper) | Up to 25 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Multiple Conductors (with accessory) | Up to 3 x 16 mm² rigid or 3 x 10 mm² flexible |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 3.5 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26F71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 1.8 cm × L 9.5 cm; weight 119 g |
Package 2 (Box of 12) | 12 units; H 7.8 cm × W 9.8 cm × L 22.2 cm; weight 1.497 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 16.976 kg |
Carbon Footprint (Lifecycle) | |
Total | 21 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 19 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |