The MPC4 Machinery Protection Card is a core component of the Meggitt Vibro-Meter VM600 series Machinery Protection System (MPS). The model 200-510-071-113 indicates a firmware version of 071 and a hardware version of 113. This version is an earlier model, not RoHS compliant, and features a buffered dynamic signal output impedance of 2000Ω. This card is a powerful and highly flexible online monitoring and protection unit, specifically designed for the real-time, continuous monitoring of critical operating parameters of industrial rotating machinery (such as steam turbines, compressors, generators, pumps, and fans). It promptly issues alerts or triggers shutdown protection upon parameter anomalies, effectively preventing equipment damage, ensuring production safety, and reducing unplanned downtime.


The MPC4 card must be used as a pair with a matching IOC4T input/output card to form a complete monitoring channel processing unit. This card pair can operate independently or be integrated into a VM600 rack to build a centralized, distributed machinery protection and monitoring system.

2. Key Features and Benefits

  • Powerful Processing Capability: Utilizes advanced Digital Signal Processor (DSP) technology to simultaneously process 4 dynamic signal channels (vibration, displacement, dynamic pressure, etc.) and 2 speed/phase reference channels. All channels are independently programmable.

  • Comprehensive Signal Processing: Supports programmable Broadband and Narrowband (Tracking) filtering. Provides multiple rectification methods (True RMS, Mean, True Peak, True Peak-to-Peak). In order tracking mode, enables simultaneous amplitude and phase monitoring.

  • Flexible Protection Logic:

    • Fully programmable Alert and Danger setpoints per channel, with adjustable delay, hysteresis, and latching.

    • Supports Adaptive Monitoring, where Alert and Danger limits are automatically adjusted based on speed or other process parameters, ideal for start-up and coast-down phases.

    • Supports Direct Trip Multiply (TM) and Danger Bypass (DB) functions (Note: Not supported on the safety version, MPC4SIL).

    • Provides powerful alarm logic combination (up to 8 basic and 4 advanced logic functions) for implementing interlock protection based on multiple parameters.

  • Integrated Sensor Support: On-board integrated power supplies for various sensors and signal conditioners such as IEPE accelerometers and proximity probe systems, simplifying system wiring.

  • Advanced Diagnostics and Safety:

    • Built-in "OK System" continuously monitors the health of the sensor and signal chain, detecting faults like open circuits or short circuits.

    • Supports Channel Inhibit function, allowing safe maintenance of a single channel's sensor while the system is running, without affecting the protection functions of other channels (Note: Not supported on the safety version, MPC4SIL).

    • Features comprehensive Built-In Test Equipment (BITE) and overload checking.

  • Convenient Commissioning and Analysis:

    • Front-panel BNC connectors provide easy access to buffered sensor "raw" signals for connection to oscilloscopes or other analysis instruments.

    • Front-panel features rich multicolored LED status indicators for real-time display of overall card status, per-channel signal validity, alarm/danger status, and system faults.

    • Supports hot-swapping, enabling card replacement without system power-down, improving system availability and maintainability.

  • Multiple Outputs and Integration:

    • Processed signals are available as analog outputs (0-10 V or 4-20 mA) via the IOC4T card.

    • Alarm signals can drive local relays on the IOC4T card or, via the VM600 rack's OC bus, drive additional relay cards (e.g., RLC16 or IRC4).

    • Software configuration and communication via RS-232 serial port (front panel) or VME bus (via a CPUx card in the rack). Note: Model 200-510-071-113 supports VME bus configuration.

3. Applications

The MPC4 card pair is widely used in industrial sectors requiring highly reliable machinery protection, including but not limited to:

  • Power Generation: Steam turbines, gas turbines, generators, feedwater pump sets.

  • Oil & Gas: Centrifugal/reciprocating compressors, pumps, gas turbine-driven equipment.

  • Process Industries: Large fans, extruders, rolling mills.

  • Marine Propulsion: Main propulsion turbines, gearboxes.

Its primary functions are machinery protection and basic condition monitoring, ensuring equipment operates within safe parameters.

4. Operating Principle Summary

The MPC4 card's workflow is a closed loop of real-time signal acquisition, processing, monitoring, and output:

  1. Signal Acquisition & Conditioning: Sensor signals (vibration, displacement, speed, etc.) are connected via the IOC4T card. The MPC4 performs initial amplification/attenuation and separates the signal's AC and DC components for processing.

  2. Digital Signal Processing: The AC component undergoes processing via programmable gain amplifiers, optional analog integrators (for acceleration to velocity), anti-aliasing filtering, and conversion to digital by a high-speed ADC. The DSP performs digital filtering (broadband/narrowband), secondary integration/differentiation (if needed), and rectification (RMS, Peak, etc.) calculations. The DC component is used for measuring static parameters like gap and position.

  3. Monitoring & Alarm Generation: Processed signal values are compared to user-configured Alert/Danger limits. Combined with adjustable delays and hysteresis, the card determines if an alarm should be triggered. Simultaneously, the OK System continuously checks the DC signal level to ensure sensor chain integrity.

  4. Logic Combination & Output: Individual channel alarm states can be further combined using Basic and Advanced logic functions to generate complex protection logic. Ultimately, alarm signals drive relays, and processed analog values are output via the IOC4T.

5. System Self-Checks & Status Indication

The MPC4 card features comprehensive self-diagnostic capabilities:

  • Power-Up Self-Test: Checks hardware such as memory and timers.

  • Watchdog: Continuously monitors software operation to prevent hangs.

  • OK System: As described, ensures signal chain integrity.

  • Overload Check: Monitors each channel's input for saturation.


Its front-panel LEDs provide intuitive status indication:

  • DIAG/STATUS (Global Diagnostic): Multicolored LED indicating overall card status (e.g., normal operation, configuring, hardware fault, DB/TM function active).

  • Channel Status Indicators (one per channel): Multicolored LEDs indicating channel configuration status, signal validity (OK System), alarm (yellow) or danger (red) status, and channel inhibit status (slow green blink).


Category Specification Description / Notes
Dynamic Signal Inputs

Number of Inputs 4 Per MPC4 card.
Input Type Voltage or Current Supports voltage (AC+DC) and current signals.
DC Range 0 to +20 V or 0 to -20 V
AC Range ±10 V (max.)
Common Mode Voltage Range -50 V to +50 V
Input Impedance 200 kΩ For voltage inputs.
Current Input Range (DC) 0 to 25 mA
Current Input Range (AC) ±8 mA (max.)
Analog Frequency Range DC to 60 kHz (-3 dB) Applicable when Raw bus is shared.
Analog AC Frequency Range Without integration: 0.1 Hz to 10 kHz
With integration: 2.5 Hz to 10 kHz

Current Measuring Resistor 324.5 Ω For current-to-voltage conversion.
Speed/Phase Ref. Inputs (Standard & Sep. Circuits only) Not supported on Safety (MPC4SIL) version
Number of Inputs 2 Per MPC4 card.
Triggering Method Threshold crossing on rising/falling edge
Trigger Thresholds Rising = (2/3) × Vpp, Falling = (1/3) × Vpp
Tachometer Range Input: 0.016 Hz to 50 kHz
After division: 0.016 Hz to 1092 Hz (1 to 65535 RPM)

Input Voltage Range 0.3 Hz to 10 kHz: 0.4 to 500 Vpp
10 kHz to 50 kHz: 2.0 to 500 Vpp

Buffered Signal Outputs

Output Type "Raw" dynamic and speed signals Front-panel BNC (MPC4) and screw terminals (IOC4T).
Output Impedance 2000 Ω Characteristic of earlier model 200-510-071-113. Later RoHS compliant models are 50Ω.
Dynamic Channel Transfer Ratio Voltage Input: 1 V/V
Current Input: 0.3245 V/mA

Speed Channel Output 0 to 5 V TTL-compatible signal Front-panel BNC output.
Analog (DC) Outputs (Provided by IOC4T card)
Number of Outputs 4 (DC OUT 1-4)
Signal Type 4 to 20 mA or 0 to 10 V Selected via jumper.
Extended Linear Range Can extend beyond nominal range, maintaining linearity Approx. 0 to 23.1 mA, -2.5 to 11.9 V.
Processing Functions

Broadband Processing High-pass, Low-pass, or Band-pass filtering Slope configurable from 6 to 60 dB/octave.
Narrowband (Tracking) Proc. Constant Q filter (Q=28) Standard & Sep. Circuits only. Supports order extraction (1/3X, 1/2X, 1X, 2X, 3X, 4X).
Relative Shaft Vibration Proc. Freq. Range: Vib. 0.1 Hz - 10 kHz, Gap/Pos. DC - 1 Hz Provides initial gap/offset compensation.
Amplitude Accuracy ±1% of full scale (typical)
Linearity Error ≤ ±1%
Alarm & Logic

Alarm Levels Alert+, Alert-; Danger+, Danger- Per measurement channel. Speed channels have Alert+, Alert- only.
Alarm Parameters Delay, Hysteresis, Latching all programmable
Adaptive Monitoring Supported Alarm limits dynamically adjusted based on speed, etc.
Direct Trip Multiply (TM) Supported Multiplier coefficient (0.1-5.0) switched via external DSI signal. Not on Safety version.
Danger Bypass (DB) Supported Temporarily inhibits Danger relay action via external DSI signal. Not on Safety version.
Channel Inhibit Supported Temporarily disables protection output of a specified channel. Not on Safety version.
Logic Combinations 8 Basic + 4 Advanced Logic functions Supports AND, OR, Majority Voting, etc.
OK System Check

Function Monitors sensor and line health Detects faults like open circuit, short circuit.
Check Type Two configurable thresholds (Upper & Lower)
Confirmation Time 250 ms Prevents noise spikes from causing false triggers.
Response Time < 100 ms
Electrical & Environmental

Power Input +5 VDC, ±12 VDC Supplied by VM600 rack.
Typical Power Consumption +5V: 12.5W + ~1W per sensor
±12V: Max 2.5W

Sensor Power Supply Output +27.2V, -27.2V, +15.0V (all ±5%) Each 0-25 mA.
Operating Temperature -25°C to +65°C
Storage Temperature -40°C to +85°C
Operating Humidity 0 to 90%, non-condensing
Communications & Config.

Configuration Interface RS-232 Serial Port (front panel)
VME Bus (via CPUx card)
Model 200-510-071-113 supports VME bus. Safety version supports RS-232 only.
Communication Protocols Ethernet and Fieldbus supported via CPUx card
MPC4↔IOC4T Bus Dedicated bus similar to Industry Pack (IP)
Physical Characteristics

Dimensions (H x W x D) 6U x 20 mm x 187 mm Approx. 262 mm x 20 mm x 187 mm
Weight Approx. 0.40 kg
Approvals & Compliance (Depends on specific version) 200-510-071-113 is a non-RoHS compliant model.
EMC IEC/EN 61000-6-2, IEC/EN 61000-6-4
Electrical Safety IEC/EN 61010-1
Functional Safety Standard & Safety versions compliant with IEC 61508 (SIL 1) & ISO 13849-1 (PL c)
Previous: 
Next: 

Quick Links

PRODUCTS

OEM

Contact Us

 Telephone: +86-181-0690-6650
 WhatsApp: +8618106906650
 Email:  sales2@exstar-automation.com / lily@htechplc.com
 Address: Room 1904, Building B, Diamond Coast, No. 96 Lujiang Road, Siming District, Xiamen Fujian, China
Copyright © 2025 Exstar Automation Services Co., Ltd. All Rights Reserved.