The A9F73106 is a 6‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N series, featuring a B‑curve tripping characteristic (magnetic threshold at 4 × In). The B‑curve is specifically engineered for circuits with negligible or very low inrush currents – typical of lighting banks, resistive heating elements, and general‑purpose socket outlets – delivering precise overload and short‑circuit protection without nuisance tripping. Rated with an ultimate breaking capacity of 10 kA at 220‑240 V AC per the industrial EN/IEC 60947‑2 standard and 6 kA at 230 V AC under the residential EN/IEC 60898‑1 norm, this MCB offers reliable fault clearance across diverse installation environments. It meets both standards, making it equally suitable for commercial distribution boards, industrial control panels, and domestic consumer units. The breaker incorporates the field‑proven VisiTrip indicator window, which instantly flags the tripped pole to minimise diagnostic downtime, and the VisiSafe green strip that provides positive visual evidence of contact separation – a crucial safety check for maintenance staff. Its quick‑make/quick‑break mechanism, independent of toggle position, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it saves valuable enclosure space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm², with a 2 N·m tightening torque. The device offers IP20 protection at the terminals and IP40 when housed in a modular enclosure, operates flawlessly from -35 °C to +70 °C, and is built with halogen‑free plastics, PVC‑free materials, and a 54% recyclability rate – all contributing to a total lifecycle carbon footprint of only 8 kg CO₂ eq., reflecting Schneider Electric’s eco‑design philosophy.
Parameter | Details |
|---|---|
General | |
Product Model | A9F73106 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 6 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | B |
Magnetic Tripping Limit | 4 x In ± 20% (typical) |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) – EN/IEC 60947‑2 | |
– AC 12…60 V 50/60 Hz | 36 kA |
– AC 100…133 V 50/60 Hz | 20 kA |
– AC 220…240 V 50/60 Hz | 10 kA |
– DC 12…60 V | 15 kA |
– DC 60…72 V | 10 kA |
Breaking Capacity (Icu) – EN/IEC 60898‑1 | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) – EN/IEC 60947‑2 | |
– AC 10…60 V | 27 kA (75% x Icu) |
– AC 100…133 V | 15 kA (75% x Icu) |
– AC 220…240 V | 7.5 kA (75% x Icu) |
– DC 12…60 V | 15 kA (100% x Icu) |
– DC 60…72 V | 10 kA (100% x Icu) |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 1.7 cm × W 7.3 cm × L 9.2 cm; weight 108 g |
Package 2 (Box of 12) | 12 units; H 8.2 cm × W 10.0 cm × L 22.4 cm; weight 1.360 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 15.436 kg |
Carbon Footprint (Lifecycle) | |
Total | 8 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 7 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |