Schneider
A9F76225
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F76225 is a 25‑ampere, double‑pole (2P) miniature circuit breaker from Schneider Electric’s Acti9 iC60N range, featuring a B‑curve tripping characteristic (magnetic threshold at 4 × In). The B‑curve is specifically tailored for circuits with minimal or negligible inrush currents – such as lighting, resistive heating loads, and general‑purpose distribution – where precise overload protection is paramount and nuisance tripping must be avoided. As a 2‑pole device with both poles protected, it ensures simultaneous disconnection of both lines in single‑phase AC systems or DC applications, providing enhanced safety and isolation integrity. This MCB delivers a robust ultimate breaking capacity of 20 kA at 220‑240 V AC under the industrial standard EN/IEC 60947‑2 (with higher ratings at lower voltages) and 6 kA at 400 V AC per the residential norm EN/IEC 60898‑1, ensuring reliable fault interruption in a wide range of commercial, industrial, and residential installations. Certified to both standards, it offers flexible integration into mixed‑use projects. Designed with Class‑2 insulation for superior operator protection, the breaker also coordinates fully with Acti 9 RCDs and Compact NSX MCCBs, simplifying system architecture. The device features the intuitive VisiTrip fault‑finder window, which instantly identifies the tripped pole to accelerate troubleshooting, and the VisiSafe green strip that delivers unmistakable visual confirmation of contact opening – a critical safety check for maintenance personnel. Its quick‑make/quick‑break mechanism, independent of handle position, ensures consistent performance over 10,000 electrical and 20,000 mechanical cycles. Despite its 25 A rating, the breaker maintains a compact 36 mm width (4 modular pitches) and clips onto DIN rails, saving valuable panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm² with a 2 N·m tightening torque, and the device offers IP20 terminal protection and IP40 when enclosed. Operating reliably from -35 °C to +70 °C, it is built with halogen‑free plastics and PVC‑free materials, achieving a 54% recyclability rate and a total lifecycle carbon footprint of 35 kg CO₂ eq. – all reflecting Schneider Electric’s commitment to sustainable, safe energy distribution.
Parameter | Details |
|---|---|
General | |
Product Model | A9F76225 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 2P |
Number of Protected Poles | 2 |
Rated Current (In) | 25 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | B |
Magnetic Tripping Limit | 4 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 20 kA at 220…240 V AC 50/60 Hz (from product image; higher at lower voltages per series) |
– EN/IEC 60898‑1 (AC) | 6,000 A at 400 V AC 50/60 Hz |
– DC ratings | Not specified in provided documents; refer to full datasheet |
Service Breaking Capacity (Ics) | Not explicitly stated; refer to standard series data (typically 100% or 75% of Icu) |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between phases |
Number of Pitches | 4 (36 mm total width) |
Width | 36 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.25 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…10 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Separate add‑on block required |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.2 cm × W 3.5 cm × L 9.5 cm; weight 229 g |
Package 2 (Box of 6) | 6 units; H 8.2 cm × W 10.0 cm × L 22.5 cm; weight 1.432 kg |
Package 3 (Pallet of 66) | 66 units; H 30 cm × W 30 cm × L 40 cm; weight 16.426 kg |
Carbon Footprint (Lifecycle) | |
Total | 35 kg CO₂ eq. |
Manufacturing (A1‑A3) | 2 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 32 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.6 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |