The A9F73104 is a 4‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N range, engineered with a B‑curve tripping characteristic (magnetic trip set at 4 × In). The B‑curve is specifically designed for circuits with minimal or negligible inrush currents – such as lighting banks, resistive heating loads, and sensitive control electronics – where precise overload protection is critical and nuisance tripping must be avoided. Despite its low current rating, this MCB delivers an exceptional ultimate breaking capacity of up to 50 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard, and 6 kA at 230 V AC per the residential EN/IEC 60898‑1 norm, ensuring robust fault clearance even in high‑fault‑current scenarios. It complies with both standards, offering seamless integration across industrial control panels, commercial distribution boards, and domestic consumer units. The breaker integrates the intuitive VisiTrip fault‑finder window, which visually identifies the tripped pole to accelerate troubleshooting, and the VisiSafe green strip that provides indisputable visual proof of contact separation – a critical safety feature for maintenance personnel. Its quick‑make/quick‑break mechanism, independent of the toggle handle, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it maximises panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm², with a 2 N·m tightening torque. The device offers IP20 terminal protection and IP40 when enclosed, operates from -35 °C to +70 °C, and is built with halogen‑free plastics and PVC‑free materials, achieving a 54% recyclability rate and a total lifecycle carbon footprint of 14 kg CO₂ eq.
Parameter | Details |
|---|---|
General | |
Product Model | A9F73104 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 4 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | B |
Magnetic Tripping Limit | 4 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 50 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | < 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | < 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 50 kA (100%) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | < 15 kA (100%) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…15 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | Not specified (assumed No based on series) |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26F71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 1.8 cm × L 9.5 cm; weight 111 g |
Package 2 (Box of 12) | 12 units; H 3.03 cm × W 30.0 cm × L 20.0 cm; weight 1.399 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 15.877 kg |
Carbon Footprint (Lifecycle) | |
Total | 14 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 13 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |