The A9V35463 is a four‑pole add‑on residual current device (RCD) from Schneider Electric’s Acti9 Vigi iC60 range, designed to be paired with Acti9 iC60 or Reflex iC60 miniature circuit breakers. It provides earth‑leakage protection for personnel and equipment in three‑phase AC installations, featuring a 300 mA sensitivity and a selective (time‑delayed) trip response that ensures discrimination with downstream RCDs. Its Type A‑SI (Super Immunised) classification delivers high immunity to nuisance tripping caused by harmonics, surges, and polluted or corrosive environments, while voltage‑independent technology guarantees reliable operation even during supply fluctuations. The device protects against indirect contact electric shock and fire hazards, and its VisiTrip indicator clearly shows the faulted circuit to speed up maintenance. With a compact 135 mm width (7 modules), DIN‑rail mounting, and a rated operational voltage of 230–415 V AC, it integrates easily into industrial, commercial, and tertiary distribution boards. The RCD is discontinued as of 23 September 2025.
Parameter | Details |
|---|---|
General | |
Product Model | A9V35463 |
Range | Acti9 |
Product Name | Acti9 Vigi iC60 |
Product Type | Add‑on residual current device (RCD) |
Device Short Name | Vigi iC60 |
Poles Description | 4P |
Rated Current (In) | 63 A |
Earth‑leakage Sensitivity | 300 mA |
Earth‑leakage Protection Time Delay | Selective |
Earth‑leakage Protection Type | Type A‑SI (Super Immunised) |
Electrical | |
Network Type | AC |
Network Frequency | 50/60 Hz |
Rated Operational Voltage (Ue) | 230…415 V AC 50/60 Hz (conforming to EN/IEC 61009‑1 and EN/IEC 61009‑2‑1) |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (IEC 60947‑2) |
Residual Current Tripping Technology | Voltage‑independent |
Electromagnetic Compatibility | 8/20 μs impulse withstand, 3000 A (IEC 61009‑1) |
Standards & Compliance | |
Standards | EN/IEC 61009‑1, EN/IEC 61009‑2‑1 |
EU RoHS Directive | Compliant by exemption |
REACH Regulation | Contains SVHC above threshold |
SCIP Number | B078722f‑7853‑4e1e‑a05b‑29638f57b0ab |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
PFAS | Contains PFAS chemicals |
Compatibility & Mounting | |
Compatible Ranges | Acti9 iC60, Acti9 Reflex iC60 |
Device Location in System | Outgoer |
Mounting Mode | Clip‑on (DIN rail) |
Electrical Connection to MCB | By screw terminals (tunnel type) |
Comb Busbar Compatibility | Bottom: YES |
Modular Pitches | 7 (135 mm width) |
Physical Dimensions | |
Width | 135 mm (7 pitches of 9 mm) |
Height | 91 mm |
Depth | 73.5 mm |
Net Weight | 0.245 kg |
Terminals & Wiring | |
Connection Type | Tunnel‑type terminal (bottom) |
Rigid Conductor (without cable end) | 1…35 mm² |
Flexible Conductor (without cable end) | 1…25 mm² |
Flexible with Cable End | 1…25 mm² |
Wire Stripping Length | 14 mm (bottom) |
Tightening Torque | 3.5 N·m (bottom) |
Environmental Ratings | |
IP Degree of Protection | IP20 (terminals) / IP40 (in modular enclosure) (IEC 60529) |
Pollution Degree | 3 (IEC 60947‑2) |
Operating Temperature | -25…60 °C |
Storage Temperature | -40…85 °C |
Packaging & Logistics | |
Package 1 (Single Unit) | 1 pc; H 8.5 cm × W 12.0 cm × L 14.6 cm; weight 251 g |
Package 2 (Box of 15) | 15 units; H 30 cm × W 30 cm × L 40 cm; weight 4.32 kg |
Warranty | 18 months |
Sustainability Metrics | |
Total Lifecycle Carbon Footprint | 8 kg CO₂ eq. |
– Manufacturing (A1‑A3) | 2 kg CO₂ eq. |
– Distribution (A4) | 0 kg CO₂ eq. |
– Installation (A5) | 0.1 kg CO₂ eq. |
– Use Phase (B2, B3, B4, B6) | 6 kg CO₂ eq. |
– End‑of‑life (C1‑C4) | 0.5 kg CO₂ eq. |
Recyclability Potential | 28% |
End‑of‑life Take‑back | No |
WEEE Label | Required (separate collection in EU) |