Schneider A9V35463 Add-on residual current device, Acti9 Vigi iC60, 4P, 63A, A-SI type, selective, 300mA, 230...415VAC

  • Schneider

  • A9V35463

  • IN STOCK

  • T/T

  • XIAMEN

Availability:
Quantity:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
kakao sharing button
snapchat sharing button
telegram sharing button
sharethis sharing button

The A9V35463 is a four‑pole add‑on residual current device (RCD) from Schneider Electric’s Acti9 Vigi iC60 range, designed to be paired with Acti9 iC60 or Reflex iC60 miniature circuit breakers. It provides earth‑leakage protection for personnel and equipment in three‑phase AC installations, featuring a 300 mA sensitivity and a selective (time‑delayed) trip response that ensures discrimination with downstream RCDs. Its Type A‑SI (Super Immunised) classification delivers high immunity to nuisance tripping caused by harmonics, surges, and polluted or corrosive environments, while voltage‑independent technology guarantees reliable operation even during supply fluctuations. The device protects against indirect contact electric shock and fire hazards, and its VisiTrip indicator clearly shows the faulted circuit to speed up maintenance. With a compact 135 mm width (7 modules), DIN‑rail mounting, and a rated operational voltage of 230–415 V AC, it integrates easily into industrial, commercial, and tertiary distribution boards. The RCD is discontinued as of 23 September 2025.

Parameter

Details

General

Product Model

A9V35463

Range

Acti9

Product Name

Acti9 Vigi iC60

Product Type

Add‑on residual current device (RCD)

Device Short Name

Vigi iC60

Poles Description

4P

Rated Current (In)

63 A

Earth‑leakage Sensitivity

300 mA

Earth‑leakage Protection Time Delay

Selective

Earth‑leakage Protection Type

Type A‑SI (Super Immunised)

Electrical

Network Type

AC

Network Frequency

50/60 Hz

Rated Operational Voltage (Ue)

230…415 V AC 50/60 Hz (conforming to EN/IEC 61009‑1 and EN/IEC 61009‑2‑1)

Rated Insulation Voltage (Ui)

500 V AC 50/60 Hz (IEC 60947‑2)

Rated Impulse Withstand Voltage (Uimp)

6 kV (IEC 60947‑2)

Residual Current Tripping Technology

Voltage‑independent

Electromagnetic Compatibility

8/20 μs impulse withstand, 3000 A (IEC 61009‑1)

Standards & Compliance

Standards

EN/IEC 61009‑1, EN/IEC 61009‑2‑1

EU RoHS Directive

Compliant by exemption

REACH Regulation

Contains SVHC above threshold

SCIP Number

B078722f‑7853‑4e1e‑a05b‑29638f57b0ab

Halogen‑free (plastic parts)

Yes

PVC‑free

Yes

Silicone‑free

No

PFAS

Contains PFAS chemicals

Compatibility & Mounting

Compatible Ranges

Acti9 iC60, Acti9 Reflex iC60

Device Location in System

Outgoer

Mounting Mode

Clip‑on (DIN rail)

Electrical Connection to MCB

By screw terminals (tunnel type)

Comb Busbar Compatibility

Bottom: YES

Modular Pitches

7 (135 mm width)

Physical Dimensions

Width

135 mm (7 pitches of 9 mm)

Height

91 mm

Depth

73.5 mm

Net Weight

0.245 kg

Terminals & Wiring

Connection Type

Tunnel‑type terminal (bottom)

Rigid Conductor (without cable end)

1…35 mm²

Flexible Conductor (without cable end)

1…25 mm²

Flexible with Cable End

1…25 mm²

Wire Stripping Length

14 mm (bottom)

Tightening Torque

3.5 N·m (bottom)

Environmental Ratings

IP Degree of Protection

IP20 (terminals) / IP40 (in modular enclosure) (IEC 60529)

Pollution Degree

3 (IEC 60947‑2)

Operating Temperature

-25…60 °C

Storage Temperature

-40…85 °C

Packaging & Logistics

Package 1 (Single Unit)

1 pc; H 8.5 cm × W 12.0 cm × L 14.6 cm; weight 251 g

Package 2 (Box of 15)

15 units; H 30 cm × W 30 cm × L 40 cm; weight 4.32 kg

Warranty

18 months

Sustainability Metrics

Total Lifecycle Carbon Footprint

8 kg CO₂ eq.

– Manufacturing (A1‑A3)

2 kg CO₂ eq.

– Distribution (A4)

0 kg CO₂ eq.

– Installation (A5)

0.1 kg CO₂ eq.

– Use Phase (B2, B3, B4, B6)

6 kg CO₂ eq.

– End‑of‑life (C1‑C4)

0.5 kg CO₂ eq.

Recyclability Potential

28%

End‑of‑life Take‑back

No

WEEE Label

Required (separate collection in EU)

Previous: 
Next: 

Related Products