Schneider
A9F79125
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F79125 is a 25‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N series, featuring a C‑curve tripping characteristic (magnetic trip set at 8 × In). The C‑curve provides a well‑balanced response between thermal overload protection and tolerance of moderate inrush currents, making this device an ideal solution for general‑purpose distribution circuits – including lighting networks, socket outlets, control panels, and small motor feeders – across commercial, industrial, and residential environments. This MCB delivers a reliable ultimate breaking capacity of 10 kA at 220‑240 V AC under the EN/IEC 60947‑2 industrial standard, and 6 kA at 230 V AC per the EN/IEC 60898‑1 residential norm, ensuring robust fault protection in diverse installations. The breaker integrates the well‑known VisiTrip window, which visually flags the tripped pole to accelerate fault diagnosis, alongside the VisiSafe green strip that provides undeniable proof of contact separation – a critical safety feature for maintenance personnel. Its quick‑make/quick‑break mechanism, independent of handle position, guarantees consistent performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it maximises panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm², with a tightening torque of 2 N·m. The device offers IP20 protection at the terminals and IP40 when enclosed in a modular cabinet, operating reliably from -35 °C to +70 °C. Sustainability features include halogen‑free plastics, PVC‑free construction, and a 54% recyclability rate, with a total lifecycle carbon footprint of 17 kg CO₂ eq. – transparently disclosed in the product’s environmental profile.
Parameter | Details |
|---|---|
General | |
Product Model | A9F79125 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 25 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 36 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 27 kA (75% x Icu) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 15 kA (100% x Icu) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Product Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…10 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | Not specified (assumed No based on other models) |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26F71d1‑98cf‑4280‑8725‑455b9a6b2fb9 (case‑sensitive) |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 1.8 cm × W 7.5 cm × L 9.4 cm; weight 115 g |
Package 2 (Box of 12) | 12 units; H 8.0 cm × W 9.8 cm × L 22.5 cm; weight 1.455 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 16.432 kg |
Carbon Footprint (Lifecycle) | |
Total | 17 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 16 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |