The A9F94104 is a 4‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60L series, equipped with a C‑curve tripping characteristic (magnetic threshold at 8 × In). This C‑curve delivers a well‑balanced response between thermal overload protection and tolerance of moderate inrush currents, making it a flexible solution for general‑purpose distribution – including lighting circuits, socket outlets, control panels, and small power feeders – across commercial, industrial, and residential installations. What truly elevates this model is its outstanding ultimate breaking capacity: rated at 100 kA at 220‑240 V AC under the EN/IEC 60947‑2 industrial standard, and 15 kA at 230 V AC per the EN/IEC 60898‑1 residential norm, ensuring robust fault clearing even in high‑fault‑current environments. This MCB complies with both standards, offering seamless integration across mixed‑use projects. The device incorporates the intuitive VisiTrip fault‑finder window, which visually pinpoints the tripped pole to accelerate troubleshooting, and the VisiSafe green strip that provides unmistakable visual confirmation of contact separation – a critical safety feature for downstream maintenance. Its quick‑make/quick‑break mechanism, independent of the toggle handle, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it optimises panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm², with a 2 N·m torque. The device offers IP20 protection at the terminals and IP40 when enclosed, operating from -35 °C to +70 °C. Sustainability features include a halogen‑free status (plastic parts) and PVC‑free construction, with a 54% recyclability rate and a total lifecycle carbon footprint of 14 kg CO₂ eq., all transparently disclosed in line with Schneider Electric’s environmental commitments.
Parameter | Details |
|---|---|
General | |
Product Model | A9F94104 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60L |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 4 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 100 kA at 220…240 V AC (from product image) |
– EN/IEC 60947‑2 (DC) | Not specified in provided documents |
– EN/IEC 60898‑1 (AC) | 15,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | Not specified; refer to standard datasheet |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | Not detailed in PDF; based on series: typically 12…60 V AC, 100…133 V AC, 220…240 V AC, and DC 12…72 V – refer to full datasheet |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free status | Product contains halogen above thresholds (not halogen‑free) – from PDF |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | France (FR) – from PDF |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 1.8 cm × L 9.5 cm; weight 110 g |
Package 2 (Box of 12) | 12 units; H 8.0 cm × W 9.8 cm × L 22.5 cm; weight 1.384 kg |
Package 3 (Pallet of 132) | H 30.0 cm × W 30.0 cm × L 40.0 cm; weight 15.764 kg |
Carbon Footprint (Lifecycle) | |
Total | 14 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 13 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |