Schneider
A9F75140
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F75140 is a 40‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N series, engineered with a D‑curve tripping characteristic (magnetic threshold at 12 × In). The D‑curve is specifically designed for circuits with substantial inrush currents – such as motor starters, transformers, solenoid banks, and capacitive loads – where B‑ or C‑curve breakers would be susceptible to nuisance tripping. With a robust 40 A rating, this MCB provides a rated ultimate breaking capacity of 10 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard (with higher ratings at lower voltages) and 6 kA at 230 V AC per the residential EN/IEC 60898‑1 norm, ensuring dependable fault clearance even in demanding high‑fault‑current environments. Certified to both standards, it offers versatile deployment across industrial motor control centres, commercial distribution boards, and heavy‑duty residential applications. Designed with Class‑2 insulation for enhanced operator safety, the breaker also coordinates fully with Acti 9 RCDs and Compact NSX MCCBs, streamlining system design. The device incorporates the intuitive VisiTrip fault‑finder window, which instantly highlights the tripped pole to accelerate troubleshooting, and the VisiSafe green strip that delivers unmistakable visual confirmation of contact opening – a critical safety feature for maintenance crews. Its quick‑make/quick‑break mechanism, independent of toggle position, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. Despite its high 40 A rating, the breaker retains a compact 18 mm width (2 modular pitches) and clips onto DIN rails, saving valuable panel space. The terminals are engineered for heavy‑duty wiring, accepting rigid conductors up to 35 mm² and flexible up to 25 mm² with a 3.5 N·m tightening torque. The device offers IP20 terminal protection and IP40 when enclosed, operates reliably from -35 °C to +70 °C, and is built with PVC‑free materials, though it contains halogen above thresholds. Achieving a 54% recyclability rate and a total lifecycle carbon footprint of 21 kg CO₂ eq., this MCB aligns with Schneider Electric’s sustainability objectives.
Parameter | Details |
|---|---|
General | |
Product Model | A9F75140 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 40 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | D |
Magnetic Tripping Limit | 12 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 36 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 27 kA (75% x Icu) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 15 kA (100% x Icu) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…35 mm² |
Flexible Conductor (copper) | 1…25 mm² |
Flexible with Ferrule (copper) | Up to 25 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Multiple Conductors (with accessory) | Up to 3 x 16 mm² rigid or 3 x 10 mm² flexible |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 3.5 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free status | Product contains halogen above thresholds (not halogen‑free) |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 2.0 cm × W 7.5 cm × L 9.5 cm; weight 125.8 g |
Package 2 (Box of 12) | 12 units; H 8.5 cm × W 10.0 cm × L 22.5 cm; weight 1.548 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 17.434 kg |
Carbon Footprint (Lifecycle) | |
Total | 21 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 19 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.4 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |