Schneider
A9F75102
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F75102 is a 2‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N series, equipped with a D‑curve tripping characteristic (magnetic threshold at 12 × In). The D‑curve is specifically designed for circuits that experience substantial inrush currents – such as small transformers, solenoid valves, capacitive loads, and motor starters – where lower‑curve breakers (B or C) would be prone to nuisance tripping. Despite its low 2 A rating, this MCB delivers an outstanding ultimate breaking capacity of 50 kA at 220‑240 V AC under the industrial standard EN/IEC 60947‑2, and 6 kA at 230 V AC per the residential norm EN/IEC 60898‑1, ensuring reliable fault interruption even in high‑fault‑current environments. Certified to both standards, it offers flexible deployment across industrial control panels, commercial distribution boards, and specialised residential applications. The breaker incorporates the proven VisiTrip fault‑finder window, which visually pinpoints the tripped pole to shorten diagnostic time, and the VisiSafe green strip that provides clear evidence of contact separation – a critical safety feature for maintenance crews. Its quick‑make/quick‑break mechanism, independent of toggle position, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail mounting, it saves panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm² with a 2 N·m torque, and the device offers IP20 terminal protection and IP40 when enclosed, operating reliably from -35 °C to +70 °C. Built with halogen‑free plastics and PVC‑free materials, it achieves 54% recyclability and a total lifecycle carbon footprint of 11 kg CO₂ eq., reflecting Schneider Electric’s eco‑design approach.
Parameter | Details |
|---|---|
General | |
Product Model | A9F75102 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 2 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | D |
Magnetic Tripping Limit | 12 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 50 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 50 kA (100%) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 15 kA (100%) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 1.8 cm × L 9.4 cm; weight 120 g (PDF shows "12.000g" likely typo, but actual ~120 g) |
Package 2 (Box of 12) | 12 units; H 8.0 cm × W 9.8 cm × L 22.5 cm; weight 1.401 kg |
Package 3 (Pallet of 132) | H 30.0 cm × W 30.0 cm × L 40.0 cm; weight 16.124 kg |
Carbon Footprint (Lifecycle) | |
Total | 11 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 10 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |