The A9F94170 is an ultra‑low‑current, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60L range, designed with a C‑curve tripping characteristic (magnetic trip at 8 × In) and a rated current of just 0.5 A. This MCB is purpose‑built for the most sensitive electrical circuits – including control transformers, electronic power supplies, instrumentation, signalling loops, and PLC input/output modules – where even small overcurrents can damage costly components and where standard‑rated breakers offer insufficient protection. The C‑curve provides a balanced response, tolerating harmless transient surges while ensuring rapid clearance of genuine fault currents. Despite its minimal rating, this breaker delivers a remarkable ultimate breaking capacity of 100 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard (with derated values for other voltages), and 15 kA at 230 V AC per the residential EN/IEC 60898‑1 norm – guaranteeing reliable fault interruption even in high‑fault‑current environments. It is certified to both standards, offering seamless integration across industrial automation panels, commercial control cabinets, and specialised residential metering systems. The device incorporates the proven VisiTrip fault indicator, which instantly highlights the tripped pole for rapid diagnosis, and the VisiSafe green strip that provides unmistakable visual confirmation of contact opening – a vital safety check for any maintenance intervention. Its quick‑make/quick‑break mechanism, independent of handle position, ensures consistent performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail mounting, it saves valuable panel space. The double‑tunnel terminals accept conductors up to 25 mm² (rigid) and 16 mm² (flexible) with a 2 N·m torque, and the breaker offers IP20 terminal protection and IP40 when enclosed, operating reliably from -35 °C to +70 °C. Built with halogen‑free plastics and PVC‑free materials, it achieves 54% recyclability and a total lifecycle carbon footprint of 14 kg CO₂ eq.
Parameter | Details |
|---|---|
General | |
Product Model | A9F94170 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60L |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 0.5 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 100 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | < 25 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | < 15,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 100 kA (100%) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | < 25 kA (100%) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…10 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26F71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 1.7 cm × L 9.3 cm; weight 112 g |
Package 2 (Box of 12) | 12 units; H 8.0 cm × W 9.7 cm × L 22.0 cm; weight 1.395 kg |
Package 3 (Pallet of 132) | H 30.0 cm × W 30.0 cm × L 40.0 cm; weight 15.832 kg |
Carbon Footprint (Lifecycle) | |
Total | 14 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 12 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |