Schneider
A9F94110
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F94110 is a 10‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60L series, featuring a C‑curve tripping characteristic (magnetic trip at 8 × In). This C‑curve strikes an excellent balance between overload protection and tolerance of moderate inrush currents, making it a versatile choice for general lighting, power outlets, small motors, and control circuits in commercial, industrial, and residential installations. What distinguishes this model is its high short‑circuit breaking capacity – rated at 25 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard, and 15 kA at 230 V AC per the residential EN/IEC 60898‑1 norm – ensuring reliable fault clearance even in demanding environments. The MCB complies with both standards, enabling seamless use across mixed‑use projects. It incorporates the intuitive VisiTrip window, which instantly reveals the tripped pole to slash troubleshooting time, and the VisiSafe green strip that offers indisputable visual evidence of contact separation – a critical safety check for maintenance personnel. Its fast‑make/quick‑break mechanism, independent of the toggle handle, guarantees consistent performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modules) and DIN‑rail mounting, it saves valuable panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm², with a 2 N·m torque. The breaker provides IP20 terminal protection and IP40 when enclosed, operates from -35 °C to +70 °C, and features halogen‑free plastics, PVC‑free construction, a 54% recyclability rate, and a total lifecycle carbon footprint of 14 kg CO₂ eq. – all aligning with Schneider Electric’s sustainability goals.
Parameter | Details |
|---|---|
General | |
Product Model | A9F94110 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60L |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 10 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 25 kA at 220…240 V AC 50/60 Hz (as per product image) |
– EN/IEC 60947‑2 (DC) | Not specified in provided documents |
– EN/IEC 60898‑1 (AC) | 15,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | Not specified; refer to standard series datasheet |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | Not detailed in PDF; based on series: typically 12…60 V AC, 100…133 V AC, 220…240 V AC, and DC 12…72 V – consult full datasheet |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (likely Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 2.0 cm × W 7.5 cm × L 9.5 cm; weight 110 g |
Package 2 (Box of 12) | 12 units; H 8.5 cm × W 10.0 cm × L 22.5 cm; weight 1.389 kg (PDF formatting odd, but these values inferred) |
Package 3 (Pallet of 132) | H 30.0 cm × W 30.0 cm × L 40.0 cm; weight 15.683 kg |
Carbon Footprint (Lifecycle) | |
Total | 14 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 12 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |