The A9F83216 is a 16‑ampere, double‑pole (2P) miniature circuit breaker from Schneider Electric’s Acti9 iC60H series, engineered with a B‑curve tripping characteristic (magnetic threshold at 4 × In). The B‑curve is specifically designed for circuits with minimal inrush currents – such as lighting, resistive loads, and general‑purpose distribution – where precise overload protection is essential without nuisance tripping. As a 2‑pole device with both poles protected, it is ideally suited for single‑phase AC systems or DC applications requiring simultaneous disconnection of both lines, offering enhanced safety and isolation. This MCB delivers a rated ultimate breaking capacity of 30 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard, and 10 kA at 400 V AC per the residential EN/IEC 60898‑1 norm, ensuring robust fault interruption across a wide range of applications. It is certified to both standards, making it a versatile choice for commercial distribution boards, industrial control panels, and residential consumer units. Designed with Class‑2 insulation for enhanced operator safety, the breaker also coordinates seamlessly with Acti 9 RCDs and Compact NSX MCCBs. The device incorporates the intuitive VisiTrip fault‑finder window, which instantly pinpoints the tripped pole to accelerate troubleshooting, and the VisiSafe green strip that delivers unmistakable visual confirmation of contact opening – a critical safety feature for maintenance operations. Its quick‑make/quick‑break mechanism, independent of toggle position, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a width of 36 mm (4 modular pitches) and DIN‑rail clip‑on mounting, it offers efficient space utilisation in distribution panels. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm² with a 2 N·m tightening torque. The device offers IP20 terminal protection and IP40 when enclosed, operates reliably from -35 °C to +70 °C, and is built with PVC‑free materials, though it contains halogen above thresholds. Achieving a 54% recyclability rate and a total lifecycle carbon footprint of 28 kg CO₂ eq., this MCB aligns with Schneider Electric’s sustainability objectives.
Parameter | Details |
|---|---|
General | |
Product Model | A9F83216 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60H |
Device Application | Distribution |
Poles Description | 2P |
Number of Protected Poles | 2 |
Rated Current (In) | 16 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | B |
Magnetic Tripping Limit | 4 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 30 kA at 220…240 V AC (from product image; see full datasheet for other voltage ratings) |
– EN/IEC 60898‑1 (AC) | 10,000 A at 400 V AC 50/60 Hz |
– DC ratings | Not specified in provided documents |
Service Breaking Capacity (Ics) | Not specified; refer to standard series datasheet |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | Not detailed in PDF; based on series: typically 12…60 V AC, 100…133 V AC, 220…240 V AC, and DC 12…72 V – consult full datasheet |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between phases |
Number of Pitches | 4 (36 mm total width) |
Width | 36 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.25 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Separate add‑on block required |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free status | Product contains halogen above thresholds (not halogen‑free) |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 3.5 cm × W 7.5 cm × L 9.0 cm; weight 222.4 g |
Package 2 (Box of 6) | 6 units; H 8.0 cm × W 10.0 cm × L 22.5 cm; weight 1.398 kg |
Package 3 (Pallet of 66) | 66 units; H 30 cm × W 30 cm × L 40 cm; weight 15.806 kg |
Carbon Footprint (Lifecycle) | |
Total | 28 kg CO₂ eq. |
Manufacturing (A1‑A3) | 2 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 26 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.7 kg CO₂ eq. |