Schneider
A9F79106
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F79106 is a 6‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60N range, engineered with a C‑curve tripping characteristic (magnetic threshold at 8 × In). This C‑curve strikes a practical balance between overload protection and tolerance of moderate inrush currents, making it a versatile choice for general‑purpose distribution – covering lighting circuits, socket outlets, small power feeders, and control panels in commercial, industrial, and residential buildings. With a rated ultimate breaking capacity of 10 kA at 220‑240 V AC under the industrial standard EN/IEC 60947‑2 and 6 kA at 230 V AC per the residential norm EN/IEC 60898‑1, this MCB ensures reliable fault interruption across a wide range of applications. It is dual‑certified to both standards, facilitating seamless integration into mixed‑use installations. The breaker incorporates the well‑known VisiTrip fault‑finder window, which instantly highlights the tripped pole to accelerate fault diagnosis, and the VisiSafe green strip that provides unequivocal visual confirmation of contact separation – an essential safety feature for maintenance crews. Its quick‑make/quick‑break mechanism, independent of handle position, guarantees consistent switching performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it optimises panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm² with a 2 N·m torque, and the device offers IP20 protection at the terminals and IP40 when enclosed. Operating from -35 °C to +70 °C, it is built with halogen‑free plastics and PVC‑free materials, achieving a 54% recyclability rate and a total lifecycle carbon footprint of only 8 kg CO₂ eq.
Parameter | Details |
|---|---|
General | |
Product Model | A9F79106 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60N |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 6 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | C |
Magnetic Tripping Limit | 8 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 36 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 15 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 6,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 27 kA (75% x Icu) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 15 kA (100% x Icu) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…10 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | Not specified (assumed No based on series) |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26ff71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | Not specified (typically Bulgaria for iC60 series) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 1.8 cm × W 7.5 cm × L 9.5 cm; weight 109 g |
Package 2 (Box of 12) | 12 units; H 8.7 cm × W 9.8 cm × L 22.0 cm; weight 1.368 kg |
Package 3 (Pallet of 132) | H 30 cm × W 30 cm × L 40 cm; weight 15.567 kg |
Carbon Footprint (Lifecycle) | |
Total | 8 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 7 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |