The GE IS200STAIH2ABA Simplex Analog Input Terminal Board is a compact analog input terminal board used within GE Industrial Control Systems. As a member of the STAI board family, the IS200STAIH2ABA Simplex Analog Input Terminal Board accepts 10 analog inputs and 2 analog outputs and connects to the I/O pack, providing the field-side termination and signal conditioning interface for analog process signals in the Mark VIe control architecture. The board is designed to accommodate a wide variety of field transmitters, including two-wire, three-wire, four-wire, and externally powered transmitters, and supports both voltage and current input signals.

The IS200STAIH2ABA Simplex Analog Input Terminal Board is identified by the GE part numbering convention used throughout the Industrial Control Systems product line. The "IS200" prefix identifies the board as a GE Industrial Control Systems product, with "200" specifically indicating that the board is a base-level assembly. The "STAI" acronym identifies the board's functional designation as a Simplex Analog Input Terminal Board. The "H2" designation identifies the hardware group and the plug-in terminal block configuration, while the "ABA" suffix identifies the artwork and functional revision combination. All digits are important when ordering or replacing any board, as boards of different revision levels may not contain identical hardware, and GE ensures backward compatibility of replacement boards while noting that different revision levels may not contain identical components.

The IS200STAIH2ABA Simplex Analog Input Terminal Board uses high-density Euro-style box terminal blocks and includes an onboard ID chip that identifies the board to the I/O pack for system diagnostic purposes. The board revision determines compatibility with the Mark VIe PAIC and YAIC controllers: the STAIH2A variant is compatible with the Mark VIe PAIC and uses plug-in terminals, while other STAI revisions offer fixed terminals, IEC 61508 safety certification with the YAIC, or no terminal block for direct soldering. The IS200STAIH2ABA Simplex Analog Input Terminal Board is therefore part of a versatile terminal board family that can be matched to the specific controller, safety, and wiring requirements of each application.

This product introduction provides detailed technical information, functional descriptions, connector assignments, configuration guidance, and comprehensive specifications for the GE IS200STAIH2ABA Simplex Analog Input Terminal Board, serving as an essential reference for control system engineers, maintenance technicians, and system integrators working with GE industrial control equipment.

Functional Architecture and Signal Processing

The IS200STAIH2ABA Simplex Analog Input Terminal Board is built around a flexible analog signal conditioning architecture that supports multiple input types and ranges across ten analog input channels and two analog output channels. This architecture allows the board to interface with a wide variety of field instruments while providing the isolation, filtering, and scaling required for accurate measurement in industrial environments.

The ten analog inputs of the IS200STAIH2ABA Simplex Analog Input Terminal Board accommodate two-wire, three-wire, four-wire, or externally powered transmitters. Inputs 1 through 8 support ±5 V DC, ±10 V DC, or 4–20 mA signals, while inputs 9 and 10 support 4–20 mA or ±1 mA signals, providing a dedicated low-current range for specialized transmitters. The input accuracy is ±0.1% of full scale over the full operating temperature range, and the maximum lead resistance is 15 ohms two-way with a cable length of up to 300 meters (984 feet), ensuring accurate measurement even with long field wiring runs.

The two analog outputs of the IS200STAIH2ABA Simplex Analog Input Terminal Board are 0–20 mA current outputs. Only with the Mark VIe PAICH2 controller can one analog output jumper be configured to 0–200 mA current, providing a higher-current output for specialized loads. The 200 mA output is not supported by the Mark VIeS YAIC controller, so the output configuration must be matched to the controller in use. The load on the output currents is 800 ohms maximum burden for the 4–20 mA output, and 50 ohms maximum burden for the 200 mA output when using the Mark VIe PAICH2.

The board provides 24 V DC power on the terminal board for all the transmitters, eliminating the need for separate field power supplies for most two-wire transmitters. The choice of current or voltage inputs is made using jumpers, allowing each channel to be configured independently to match the connected transmitter. The onboard ID chip identifies the board to the I/O pack, enabling system diagnostics and configuration validation.

Installation and Wiring

The IS200STAIH2ABA Simplex Analog Input Terminal Board is designed for flexible installation in standard industrial cabinets. The board plus a plastic insulator mounts on a sheet metal carrier that then mounts on a DIN-rail, or optionally the board plus insulator mounts on a sheet metal assembly and then bolts directly to a cabinet. This dual mounting approach allows the board to be installed in a wide range of cabinet arrangements.

The IS200STAIH2ABA Simplex Analog Input Terminal Board has a right-angle header accepting a range of commercially available pluggable Euro-style terminal blocks, with a total of 48 terminals. This pluggable terminal block configuration simplifies field wiring and maintenance, allowing the terminal blocks to be removed for wiring and then plugged back into the board. Typically, #18 AWG wires (shielded twisted pair) are used, and an I/O cable shield terminal is provided adjacent to the terminal blocks to ensure proper shielding and grounding of the analog signal cables.

The board accommodates the following types of analog inputs and outputs: analog input from two-wire transmitters, three-wire transmitters, four-wire transmitters, and externally powered transmitters; analog input for voltage ±5 V DC and ±10 V DC; analog input for current 4–20 mA; two analog outputs of 0–20 mA current; and, only with the Mark VIe PAICH2, one analog output of 0–200 mA current. The wiring, jumper positions, and cable connections are displayed on the wiring diagram, which should be consulted during installation to ensure correct configuration.

Jumper Configuration

The IS200STAIH2ABA Simplex Analog Input Terminal Board is configured by jumpers, which allow each input and output channel to be matched to the specific field device and application requirements.

Jumpers JP1A through JP8A select either current input or voltage input for inputs 1 through 8. Jumpers JP1B through JP8B select whether the return is connected to common or is left open for inputs 1 through 8. Jumpers JP9A and JP10A select either 1 mA or 20 mA input current for inputs 9 and 10, and jumpers JP9B and JP10B select whether the return is connected to common or is left open for these two channels. Jumper JP0 sets output 1 to either 20 mA or 0–200 mA, with the 200 mA setting available only with the Mark VIe PAICH2.

The jumper settings must be verified against the wiring diagram and the specific field transmitter requirements before the board is placed in service. Incorrect jumper settings can result in inaccurate readings, out-of-range signals, or damage to the connected equipment.

Diagnostics and Board Identification

The IS200STAIH2ABA Simplex Analog Input Terminal Board provides comprehensive diagnostic capabilities that assist with system verification and fault isolation. The board provides the voltage drop across a series resistor to indicate the output current, allowing the I/O pack to monitor the output current and detect unhealthy conditions. The I/O pack creates a diagnostic alarm (fault) if any one of the eight outputs goes unhealthy, alerting the operator to a potential problem with the field wiring or the connected device.

Each cable connector on the terminal board has its own ID device that is interrogated by the I/O pack. The ID device is a read-only chip coded with the terminal board serial number, board type, revision number, and the JR, JS, or JT connector location. When this chip is read by the I/O pack and a mismatch is encountered, a hardware incompatibility fault is created, preventing the system from operating with incorrect or mismatched hardware. This diagnostic feature ensures that the correct terminal board is installed in each location and that the system configuration matches the physical hardware.

Application Suitability and System Integration

The IS200STAIH2ABA Simplex Analog Input Terminal Board is a versatile analog interface that can be used in a wide variety of GE Industrial Control System applications. Its ten analog inputs, supporting two-wire, three-wire, four-wire, and externally powered transmitters across voltage and current ranges, allow the board to interface with pressure transmitters, temperature transmitters, flow meters, level sensors, and many other analog field instruments. Its two analog outputs provide 0–20 mA or 4–20 mA current signals for valve positioners, actuators, recorders, and other analog loads, with the optional 0–200 mA output available for higher-current applications when used with the Mark VIe PAICH2.

In Mark VIe controller applications, the IS200STAIH2ABA Simplex Analog Input Terminal Board serves as the field-side termination point for the analog channels, with the I/O pack connecting to the board to acquire the analog signals and communicate with the controller over Ethernet. The board's pluggable terminal block configuration simplifies field wiring, and the onboard ID chip ensures that the correct terminal board is installed in each location and that the system configuration matches the physical hardware.

The board's DIN-rail mounting and sheet metal carrier simplify installation in standard control cabinets, and the optional direct cabinet bolt-on mounting provides additional flexibility for different cabinet arrangements. The comprehensive jumper configuration allows each input and output channel to be matched to the specific field device, ensuring accurate measurement and reliable control even in electrically noisy industrial environments.

Maintenance and Lifecycle

The IS200STAIH2ABA Simplex Analog Input Terminal Board is designed for long service life with minimal maintenance. The board contains no moving parts, and its surface-mount construction ensures high reliability in continuous industrial operation. Routine maintenance consists of periodic visual inspection of the board, terminal blocks, and wiring, verification that the jumpers are set correctly for each channel, and confirmation that the shield terminals are properly connected.

The board's diagnostic features, including the output current monitoring and the onboard ID chip, simplify troubleshooting and ensure that the correct board is installed in each location. If an output becomes unhealthy, the I/O pack generates a diagnostic alarm, alerting the operator to a potential problem with the field wiring or the connected device.

If the board requires replacement, the process is straightforward. After de-energizing the associated equipment and verifying that no power exists, the pluggable terminal blocks should be labeled and removed, and the board should be removed from its mounting. The replacement board should be installed in the same position, the jumpers set to match the original configuration, and the terminal blocks reconnected as labeled before returning the system to service.

GE Industrial Control Systems ensures compatibility of its replacement boards, even though boards of different revision levels may not contain identical hardware. When ordering a replacement IS200STAIH2ABA Simplex Analog Input Terminal Board, provide the complete part number and description, the drive or system serial number, and the Material List (ML) number. The factory may substitute later versions based on availability and design enhancements, but backward compatibility of replacement boards is guaranteed.

Conclusion

The GE IS200STAIH2ABA Simplex Analog Input Terminal Board is a reliable, robust, and versatile analog interface for GE Industrial Control Systems. Its ten analog inputs, supporting multiple transmitter types and voltage and current ranges, its two analog outputs with optional 0–200 mA capability, its comprehensive jumper configuration, and its onboard ID chip and diagnostic features provide the flexibility and reliability required for a wide range of industrial analog measurement and control applications.

With its pluggable terminal block configuration, DIN-rail or direct cabinet mounting, clearly marked jumper assignments, and comprehensive documentation, the IS200STAIH2ABA Simplex Analog Input Terminal Board is designed for easy installation, verification, and maintenance. Backed by GE's quality manufacturing, global support network, and commitment to backward compatibility, the IS200STAIH2ABA Simplex Analog Input Terminal Board continues to deliver the performance, durability, and reliability that industrial users expect from GE. Whether used in a new installation or as a replacement for an existing board, the IS200STAIH2ABA Simplex Analog Input Terminal Board provides the analog input and output functionality required for reliable and efficient control system operation.

Specification Category

Parameter

Value / Description

General

Product Name

GE IS200STAIH2ABA Simplex Analog Input Terminal Board

Board Family

STAI (Simplex Analog Input Terminal Board)

Group / Revision

H2 group, ABA revision suffix

Controller Compatibility

Mark VIe PAIC (Yes), Mark VIe YAIC (No)

Terminal Block Type

Plug-in Euro-style terminal blocks, 48 terminals

Board Identification

Onboard ID chip read by I/O pack

Analog Inputs

Number of Inputs

10

Inputs 1–8 Types

±5 V DC, ±10 V DC, or 4–20 mA

Inputs 9–10 Types

4–20 mA or ±1 mA

Transmitter Types Supported

Two-wire, three-wire, four-wire, externally powered

Input Accuracy

±0.1% of full scale over full operating temperature range

Maximum Lead Resistance

15 Ω two-way cable resistance

Maximum Cable Length

300 m (984 ft)

Analog Outputs

Number of Outputs

2

Output 1 Type

0–20 mA or 4–20 mA

Output 2 Type

0–20 mA or 4–20 mA

High-Current Output

0–200 mA, only with Mark VIe PAICH2

Output 1 Load

800 Ω max burden for 4–20 mA; 50 Ω max burden for 200 mA (PAICH2 only)

Output 2 Load

800 Ω max burden for 4–20 mA

Transmitter Power

24 V DC available on terminal board, rated at 21 mA each

Jumper Configuration

JP1A–JP8A

Current or voltage input selection for inputs 1–8

JP1B–JP8B

Return connected to common or open for inputs 1–8

JP9A–JP10A

1 mA or 20 mA input current selection for inputs 9–10

JP9B–JP10B

Return connected to common or open for inputs 9–10

JP0

Output 1 set to 20 mA or 0–200 mA (PAICH2 only)

Diagnostics

Output Current Monitoring

Voltage drop across series resistor indicates output current

Output Health Alarm

I/O pack generates diagnostic alarm if any output is unhealthy

ID Device

Read-only chip with serial number, board type, revision, JR/JS/JT connector location

Incompatibility Fault

Generated on mismatch of board type or revision

Physical and Environmental

Mounting

DIN-rail via sheet metal carrier and plastic insulator; or direct cabinet bolt-on via sheet metal assembly

Wire Size

#18 AWG shielded twisted pair (typical)

Shield Termination

I/O cable shield terminal provided adjacent to terminal blocks

Size

15.9 cm high x 10.2 cm wide (6.25 in x 4.0 in)

Technology

Surface mount

Warranty and Support

Replaceable Components

Board replaced as a unit

Warranty

As per GE Terms and Conditions

Support Contact

GE Industrial Control Systems Product Service Engineering, 1501 Roanoke Blvd., Salem, VA 24153-6492 USA

Support Phone

+1-540-387-7595

Support Fax

+1-540-387-8606

Required Info

Complete part number and description, drive or system serial number, Material List (ML) number

Ordering Information

Part Number

IS200STAIH2ABA

Part Number Breakdown

IS = GE Industrial Control Systems; 200 = base-level board; STAI = board acronym; H = group; 2 = configuration variant; A = artwork revision (backward compatible); B = functional revision 1 (backward compatible); A = functional revision 2

Ordering Note

All digits are important; factory may substitute later versions with backward compatibility

Previous: 
Next: 

Quick Links

PRODUCTS

OEM

Contact Us

 Telephone: +86-181-0690-6650
 WhatsApp: +8618106906650
 Email:  sales2@exstar-automation.com / lily@htechplc.com
 Address: Room 1904, Building B, Diamond Coast, No. 96 Lujiang Road, Siming District, Xiamen Fujian, China
Copyright © 2025 Exstar Automation Services Co., Ltd. All Rights Reserved.