Schneider
A9F95110
$116
IN STOCK
T/T
XIAMEN
| Availability: | |
|---|---|
| Quantity: | |
The A9F95110 is a 10‑ampere, single‑pole miniature circuit breaker from Schneider Electric’s Acti9 iC60L series, featuring a K‑curve tripping characteristic (magnetic threshold at 12 × In). The K‑curve is specifically engineered for circuits with pronounced inrush currents – such as transformers, solenoid valves, motor starters, and capacitive loads – where B‑ or C‑curve breakers would be prone to nuisance tripping. Rated at 10 A, this MCB delivers a proven ultimate breaking capacity of 25 kA at 220‑240 V AC under the industrial EN/IEC 60947‑2 standard (with higher ratings at lower voltages) and 15 kA at 230 V AC per the residential EN/IEC 60898‑1 norm, ensuring robust fault interruption in a wide range of applications. It is certified to both standards, making it a versatile choice for industrial automation, commercial distribution, and specialised residential installations. The breaker integrates the intuitive VisiTrip fault‑finder window, which instantly pinpoints the tripped pole to accelerate troubleshooting, and the VisiSafe green strip that provides clear visual evidence of contact separation – a critical safety feature for maintenance operations. Its quick‑make/quick‑break mechanism, independent of toggle position, guarantees consistent performance over 10,000 electrical and 20,000 mechanical cycles. With a compact 18 mm width (2 modular pitches) and DIN‑rail clip‑on mounting, it saves valuable panel space. The double‑tunnel terminals accept rigid conductors up to 25 mm² and flexible up to 16 mm² with a 2 N·m tightening torque. The device offers IP20 terminal protection and IP40 when enclosed, operates reliably from -35 °C to +70 °C, and is built with halogen‑free plastics and PVC‑free materials, achieving a 54% recyclability rate and a total lifecycle carbon footprint of 14 kg CO₂ eq., all backed by Schneider Electric’s transparent environmental disclosure. This model is manufactured in France, reflecting Schneider’s commitment to high‑quality European production standards.
Parameter | Details |
|---|---|
General | |
Product Model | A9F95110 |
Range | Acti9 |
Product Name | Acti9 iC60 |
Device Short Name | iC60L |
Device Application | Distribution |
Poles Description | 1P |
Number of Protected Poles | 1 |
Rated Current (In) | 10 A |
Network Type | AC / DC |
Trip Unit Technology | Thermal‑magnetic |
Tripping Curve | K |
Magnetic Tripping Limit | 12 x In ± 20% |
Suitability for Isolation | Yes (conforming to EN/IEC 60898‑1 and EN/IEC 60947‑2) |
Utilisation Category | Category A (EN/IEC 60947‑2) |
Breaking Capacity (Icu) | |
– EN/IEC 60947‑2 (AC) | 70 kA at 12…60 V AC 50/60 Hz |
– EN/IEC 60947‑2 (DC) | 25 kA at 12…60 V DC |
– EN/IEC 60898‑1 (AC) | 15,000 A at 230 V AC 50/60 Hz |
Service Breaking Capacity (Ics) | |
– EN/IEC 60947‑2 (AC) | 35 kA (50% x Icu) at 12…60 V AC |
– EN/IEC 60947‑2 (DC) | 25 kA (100% x Icu) at 12…60 V DC |
Limitation Class | Class 3 (EN/IEC 60898‑1) |
Rated Operational Voltage (Ue) | 12…60 V AC 50/60 Hz |
Rated Insulation Voltage (Ui) | 500 V AC 50/60 Hz (EN/IEC 60947‑2) |
Rated Impulse Withstand Voltage (Uimp) | 6 kV (EN/IEC 60947‑2) |
Network Frequency | 50/60 Hz |
Durability | |
Mechanical Durability | 20,000 cycles |
Electrical Durability | 10,000 cycles |
Contact Position Indicator | Yes (toggle) |
Local Signalling | Trip indicator (VisiTrip) |
Mounting & Physical | |
Mounting Mode | Clip‑on (35 mm DIN rail) |
Removable Comb Busbar | Installed; compatible top or bottom |
Connection Pitch | 18 mm between devices |
Number of Pitches | 2 (18 mm total width) |
Width | 18 mm |
Height | 85 mm |
Depth | 78.5 mm |
Net Weight | 0.215 kg |
Colour | White (RAL9003) |
Terminals & Connections | |
Connection Type | Single terminal (top or bottom), double tunnel |
Rigid Conductor (copper) | 1…25 mm² |
Flexible Conductor (copper) | 1…16 mm² |
Flexible with Ferrule (copper) | 1…16 mm² |
With Ring Terminal (Cu/Al) | Via accessory |
Wire Stripping Length | 14 mm (top or bottom) |
Tightening Torque | 2 N·m (top or bottom) |
Earth‑leakage Protection | Without (separate add‑on block required) |
Environmental & Protection Ratings | |
Standards Compliance | EN/IEC 60947‑2, EN/IEC 60898‑1 |
IP Degree (terminals) | IP20 (IEC 60529) |
IP in Enclosure | IP40 (Insulation class II) |
Pollution Degree | 3 (EN/IEC 60947‑2) |
Overvoltage Category | IV |
Tropicalisation | 2 (IEC 60068‑1) |
Relative Humidity | 95% at 55°C |
Operating Altitude | 0…2000 m |
Operating Temperature | -35°C … +70°C |
Storage Temperature | -40°C … +85°C |
Sustainability & Compliance | |
Halogen‑free (plastic parts) | Yes |
PVC‑free | Yes |
Silicone‑free | No |
Recyclability Potential | 54% |
EU RoHS Directive | Compliant |
REACH SVHC | Contains SVHC above threshold |
SCIP Number | 26F71d1‑98cf‑4280‑8725‑455b9a6b2fb9 |
Packaging with recycled cardboard | Yes |
Packaging without single‑use plastic | Yes |
WEEE Label | Required for EU disposal (separate collection) |
Repair / Take‑back | No / No |
Logistics | |
Country of Origin | France (FR) |
Warranty | 18 months |
Package 1 (Single unit) | 1 pc; H 7.5 cm × W 1.7 cm × L 9.4 cm; weight 110 g |
Package 2 (Box of 12) | 12 units; H 7.8 cm × W 9.7 cm × L 22.0 cm; weight 1.379 kg |
Package 3 (Pallet of 132) | H 30.0 cm × W 30.0 cm × L 40.0 cm; weight 15.867 kg |
Carbon Footprint (Lifecycle) | |
Total | 14 kg CO₂ eq. |
Manufacturing (A1‑A3) | 0.8 kg CO₂ eq. |
Distribution (A4) | 0 kg CO₂ eq. |
Installation (A5) | 0 kg CO₂ eq. |
Use Phase (B2, B3, B4, B6) | 12 kg CO₂ eq. |
End‑of‑life (C1‑C4) | 0.3 kg CO₂ eq. |
Environmental Disclosure | Product Environmental Profile available |